Chapter 16. Captive (emergency) power
generation
INR 380 / US $ 10
Introduction
DG set
Operating parameters
Theory of operation
Guidelines on the selection of a DG set
Types of loads
Starting of a DG set
Protection of a DG set
Parallel operation
Procedure of parallel operation
Fault levels and grounding of generators
Recommended protection for a synchronizing scheme
Load sharing by two or more generators
Total automation through PLCs
APPENDIX Selection of power cables PVC, paper insulated and XLPE and
ampacity
Introduction
It is common practice to provide a standby emergency source of supply at
all important installations such as large factories, railways, airports,
hospitals and other essential services. This is usually achieved with the
use of a captive diesel generator (DG) set (Figure 16.1). Here we briefly
discuss these machines, their characteristics and selection for a required
application. We also consider schemes that are commonly used to start a
DG set and run it individually or in parallel with an existing source of
supply, which may be another DG set or an infinite bus.
Ground fault level
Solid grounding
Generators have a different grounding practice from others due to their
zero phase sequence reactance, which is much less than its positive or negative
phase sequence reactances (Section 13.4.1(5) and Table 13.6). See the above
example where x0 is only 4.1% compared to as 16.2%. As a result,
the ground fault current in a generator circuit is much greater than its
three-phase symmetrical fault current. This current rises further when they
are individually grounded and more than one unit are running in parallel
at a time. It is worth mentioning that when two or more generators are running
in parallel and all of them are grounded, they form a closed circuit to
cause circulating current. This may occur even in a healthy system due to
unbalance, not because of single-phase loads but unequal generator phase
currents due to eddy currents. These are important aspects and must be considered
while deciding on the grounding method of a solidly grounded generator.
Appendix 16.1
Introduction
To provide a reference for those working on power projects or at sites,
we provide some important data on different types of LV and HV power cables
in this appendix. The cables described here are in use for all kinds of
power distribution applications. of these, XLPE cables are also used for
power transmission applications. To help a user select the most appropriate
types of cables, we also provide a brief comparative chart of the various
types of cables being manufactured. Tables giving the technical particulars
of such cables in all voltage ratings have also been provided.
The selection process of power cables is almost the same as that of a bus
system discussed in Section 28.3. For simplicity we consider only the basic
data for selection which would suffice the majority of applications. For
accurate calculations a similar approach will be essential as for the bus
systems (Chapter 28). For site conditions and laying arrangements which
may influence the basic rating of a cable, corresponding derating factors
have also been provided. The information covered here will be useful to
users to meet their cable requirements, although the data may vary marginally
for different manufacturers. For more data on cables, not covered here,
reference may be made to the cable manu-facturers.
The choice of any of the cables mentioned in Table A16.1 will depend upon
the site conditions, fault level and the voltage rating of the system. A
brief comparison of all these insulating systems is given in Table A16.2.
INR 380 / US $ 10